Author: Caesar Wiratama, M.S
PT Tensor Karya Nusantara, wiratama@pt-tensor.com
Abstract. This report documents an OpenFOAM recreation of the three-rack CEETHERM rack-level cold/hot-aisle benchmark of Saiyad, Fulpagare and Bhargav (Building Simulation, 2022). Steady buoyant airflow is solved with buoyantBoussinesqSimpleFoam and RAS RNGkEpsilon on a structured hex mesh. Geometry follows a 2.2 × 1.82 × 1.98 m domain with porous mid-rack simulators and neighbouring racks, open overhead cold–hot connection, tile inlet (1.54 m/s, 17 °C), and hot-aisle ceiling return. Server heat and Darcy–Forchheimer resistances follow Table 2; exit-fan effects are approximated with meanVelocityForce on thin hot-face cell zones. Validation compares CFD rack inlet/outlet temperatures against digitised experimental markers from the reference paper.



Cite: DOI 10.13140/RG.2.2.15397.67044
Publisher: Tensor Publisher

